Allowable Ampacities of Insulated
Conductors
The following table is provided for your convenience.
We believe that the data presented is reliable, however we make no claim as to
the accuracy of the information.
|
Applicable To Conductors:
-
Rated 0
Through 2000 Volts
-
60°C
Through 90°C (140°F Through 194°F)
-
Not More
Than Three Current-Carrying Conductors in
Raceway, Cable, or Earth (Directly Buried)
-
Ambient
Temperature of 30°C (86°F)
|
|
COPPER |
ALUMINUM |
Conductor
Size
AWG or kcmil |
Allowable
Ampacities* |
Allowable
Ampacities* |
Conductor
Size
AWG or kcmil |
| 60°C |
75°C |
90°C |
60°C |
75°C |
90°C |
| |
|
TYPES THWN, RHW, USE
|
TYPES THWN-2, USE-2, XHHW-2, XHHW, RHW-2,
RHH |
|
TYPES THWN, RHW, USE
|
TYPES THWN-2, USE-2, XHHW-2, XHHW, RHW-2,
RHH |
|
|
8 |
40 |
50 |
55 |
30 |
40 |
45 |
8 |
| 6 |
55 |
65 |
75 |
40 |
50 |
60 |
6 |
| 4 |
70 |
85 |
95 |
55 |
65 |
75 |
4 |
| 2 |
95 |
115 |
130 |
75 |
90 |
100 |
2 |
| 1 |
110 |
130 |
150 |
85 |
100 |
115 |
1 |
| 1/0 |
125 |
150 |
170 |
100 |
120 |
135 |
1/0 |
| 2/0 |
145 |
175 |
195 |
115 |
135 |
150 |
2/0 |
| 3/0 |
165 |
200 |
225 |
130 |
155 |
175 |
3/0 |
| 4/0 |
195 |
230 |
260 |
150 |
180 |
205 |
4/0 |
| 250 |
215 |
255 |
290 |
170 |
205 |
230 |
250 |
| 300 |
240 |
285 |
320 |
190 |
230 |
255 |
300 |
| 350 |
260 |
310 |
350 |
210 |
250 |
280 |
350 |
| 400 |
280 |
335 |
380 |
225 |
270 |
305 |
400 |
| 500 |
320 |
380 |
430 |
260 |
310 |
350 |
500 |
| 600 |
355 |
420 |
475 |
285 |
340 |
385 |
600 |
| 700 |
385 |
460 |
520 |
310 |
375 |
420 |
700 |
| 750 |
400 |
475 |
535 |
320 |
385 |
435 |
750 |
| 1000 |
455 |
545 |
615 |
375 |
445 |
500 |
1000 |
|
*Allowable Ampacities:
30ºC (86ºF) Ambient Temperature
Based on 2005 NEC, Table
310.16.
For different ambient
temperatures than the one shown above, consult the NEC tables.
Temperature Limitations:
The temperature rating associated with the ampacity of a conductor shall
be selected and coordinated so as not to exceed the lowest temperature
rating of any connected termination, conductor, or device.
Conductors with temperature ratings higher than specified for terminations
shall be permitted to be used for ampacity adjustment, correction, or
both. |