Loop
Resistance Tables For
Thermocouple Wire
The following table is provided for your convenience. We
believe that the data presented is reliable, however we make no claim as to the
accuracy of the information.
Return
To References Home Page
DATA LOOP RESISTANCE TABLES
FOR THERMOCOUPLE WIRE - OHM/100 ft. |
| AWG |
Iron/
Constantan |
Copper/
Constantan |
Chromel/
Alumel* |
|
SOLID |
| 8 |
2.145 |
2.409 |
3.646 |
| 12 |
5.423 |
4.661 |
9.219 |
| 14 |
8.625 |
7.413 |
14.66 |
| 16 |
13.71 |
11.78 |
23.30 |
| 17 |
17.30 |
14.87 |
29.39 |
| 18 |
21.80 |
18.74 |
37.07 |
| 20 |
35.69 |
29.82 |
58.97 |
| 22 |
55.11 |
46.91 |
93.68 |
| 24 |
87.66 |
75.34 |
149.0 |
| 26 |
139.4 |
119.8 |
237.0 |
|
STRANDED |
| 14 |
7.873 |
6.767 |
13.38 |
| 16 |
12.53 |
10.77 |
21.29 |
| 17 |
18.52 |
15.92 |
31.50 |
| 18 |
19.91 |
17.11 |
33.85 |
| 20 |
34.85 |
29.95 |
59.25 |
| 22 |
50.28 |
43.21 |
85.52 |
Return
To References Home Page
|